Check Date and Time on Controller, change accordingly
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Each Device Uniquely Addressed
 
 
 
 
 
 
 
 
 
 
Each Device Shows Green (good communication) on Software
 
 
 
 
 
 
 
 
 
 
All debris cleaned and removed to trash
 
 
 
 
 
 
 
 
 
 
All components have their covers in place – no missing screws
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Check all wiring –
 
 
 
 
 
 
 
 
 
 
 
 
No loose or hanging wire or cable
 
 
 
 
 
 
 
 
 
 
No missing Contacts
 
 
 
 
 
 
 
 
 
 
Routing within device cases neat and orderly
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
All ground wires securely fastened and tested
 
 
 
 
 
 
 
 
 
 
 
 
Drain wires attached at the remote end ONLY
 
 
 
 
 
 
 
 
 
 
Strap from Keypad face to rear cover tight.
 
 
 
 
 
 
 
 
 
 
Device rear case grounded to excellent earth ground
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Door Alarms:
 
 
 
 
 
 
 
 
 
 
 
 
All Contacts glued and screwed
 
 
 
 
 
 
 
 
 
 
All contact alignment checked
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
At Mux:
 
 
 
 
 
 
 
 
 
 
 
 
DVM Shows +5V on all doors when door is Open
 
 
 
 
 
 
 
 
 
 
DVM Shows 0V on all doors when doors are Closed
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
On Computer – Using DiagnostyX
 
 
 
 
 
 
 
 
 
 
 
 
All doors report Change of State to Open
 
 
 
 
 
 
 
 
 
 
All doors report Change of State to Closed
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Sirens:
 
 
 
 
 
 
 
 
 
 
 
 
Installed at specified Location
 
 
 
 
 
 
 
 
 
 
Sounds when directed to – use DiagnostyX
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Access Controls:
 
 
 
 
 
 
 
 
 
 
 
 
Exterior units should not have wiring to gate or door
 
 
 
 
 
 
 
 
 
 
All access control open their respective access point.
 
 
 
 
 
 
 
 
 
 
Display mask enabled (if it should be)
 
 
 
 
 
 
 
 
 
 
Date/Time of the correct format
 
 
 
 
 
 
 
 
 
 
Verify Gate/Door completes cycle properly at least 3 times.
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Intercom Works properly
 
 
 
 
 
 
 
 
 
 
 
 
Intercom dials correct number
 
 
 
 
 
 
 
 
 
 
Audio is clear on each end
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Camera
 
 
 
 
 
 
 
 
 
 
 
 
Focus correct
 
 
 
 
 
 
 
 
 
 
Image appears on screen
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Monitors
 
 
 
 
 
 
 
 
 
 
 
 
Check door monitors (connected to Keypad) for proper switching using a DVM and DiagnostyX
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Special Functions and Processes:
 
 
 
 
 
 
 
 
 
 
 
 
All special processes, such as perimeter alarm shunting should be tested including the operation of the Perimeter Alarm Panel.
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Controller Set up:
 
 
 
 
 
 
 
 
 
 
 
 
Hours
 
 
 
 
 
 
 
 
 
 
Keypads
 
 
 
 
 
 
 
 
 
 
Keypad relay control ->redirected as required
 
 
 
 
 
 
 
 
 
 
Messages
 
 
 
 
 
 
 
 
 
 
NRC Units
 
 
 
 
 
 
 
 
 
 
Property Management System Selected
 
 
 
 
 
 
 
 
 
 
Unit ID's
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Graphics:
 
 
 
 
 
 
 
 
 
 
 
 
Running on screen
 
 
 
 
 
 
 
 
 
 
Scrolling smoothly
 
 
 
 
 
 
 
 
 
 
Objects change state matching facility objects